[technical analysis] causes of high surface temperature of water cooled condenser

visits:41 addtime:2023-10-11 16:37:33

n the working process of the refrigeration system, the temperature of the outer surface of the water-cooled stage condenser should be close to the normal temperature, and the hands should not feel hot. Once the surface temperature is too high, the cause should be found out and measures should be taken to eliminate this phenomenon.


Generally speaking, the main cause of condenser temperature rise is the problem of cooling water. There are usually four kinds of feelings


Situation:


1) There is not enough cooling water and water pressure. The water-cooled condenser uses cooling water to take away the latent heat released during the condensation of refrigerant vapor. Therefore, the pressure of cooling water is not enough, the flow rate can not meet the rated requirements, and the heat dissipation capacity is limited, * which eventually causes the surface temperature of the condenser to rise.


2) The cooling water temperature is too high, which is higher than the rated operating temperature (usually 32 ℃). The cooling water temperature in Vietnam, the smaller the cooling temperature difference of refrigerant, the smaller the heat transfer, the refrigerant can not be effectively cooled, and the surface temperature of condenser will rise


High.


3) The poor quality of cooling water leads to scaling on the inner wall of the cooling water pipe in the condenser, increasing the thermal resistance, affecting the heat exchange between refrigerant and cooling water, and reducing the heat transfer effect. This kind of fault often occurs in the equipment which has been used for a long time and has not been cleaned regularly. The solution is to remove scale.


4) The inlet and outlet pipes of cooling water are installed incorrectly. The normal installation position is generally low inlet pipe position and high outlet pipe position


"Low in, high out.". If the inlet pipe is set high, the cooling water can not be completely filled in the condenser, the heat transfer area will be smaller, and the refrigerant vapor can not be effectively condensed, which will make the surface temperature of the condenser rise.


When the surface temperature of the condenser increases, it means that the condensation effect is recommended, and the cooling capacity of the system will decrease.


<menuitem id="uv949"></menuitem>
  • <menuitem id="uv949"><center id="uv949"><em id="uv949"></em></center></menuitem>
        主站蜘蛛池模板: 三年成全免费观看影视大全| 欧美熟女| 欧美日韩国产在线一区二区| 一炕四女被窝交换啪啪| 少妇与公做了夜伦理69| 国产午夜精品一区二区三区嫩草| 日本无码av片在线电影网站| 连山| 日本高清aⅴ毛片免费| 丰台区| 亚洲精品一区二区久久| CHINESE国产高清AV| 南召县| 北票市| 主仆调教SM束缚绳索捆绑| 人妻洗澡被强公日日澡电影| SM调教贱屁股眼哭叫求饶H| 日本 学生?亚洲?护士| 黑巨茎大战欧美白妞| 男人添女人荫蒂视频观看| 日韩av片免费播放| 海宁市| 真人作爱90分钟免费看视频 | 欧美无砖专区一中文字| 日本国产网曝视频在线观看| 精品国产av无码一区二区三区| 福海县| 日本抽搐一进一出越深越好| 湾仔区| 鲁鲁鲁爽爽爽在线视频观看| 佛山市| 察雅县| 成全电影在线| 四川少妇BBBB槡BBBB槡| 齐齐哈尔市| 互助| 沂水县| 嫩江县| 庆安县| 蜜臀久久99精品久久久久久小说| 宕昌县|